EV Charger Installation & Wiring Guides

Precision engineering tools and installation guides for residential and commercial Level 2 EVSE, hardwired terminals, NEMA receptacles, and continuous load sizing.

Featured Calculators & Engineering Tools

NEC 625 • 125% Continuous Rule

EV Charger Wire Size Calculator

Determine code-compliant copper and aluminum conductor gauges, breaker sizing, and thermal terminal ratings for 16A to 80A Level 2 chargers with automatic 125% continuous duty derating.

Level 2 (240V) Copper / Aluminum 75°C Terminations
Calculate EV Wire Size →
Chapter 9 • Table 1

Conduit Fill Calculator

Verify trade-size raceway capacity across EMT, PVC Schedule 40/80, and Liquidtight conduit based on the NEC 40% fill limit for 3 or more conductors.

EMT / PVC / FMC 40% Fill Rule THHN / XHHW-2
Calculate Conduit Fill →

Understanding NEC Article 625 & Continuous Loads

Electric vehicle supply equipment (EVSE) is classified by NEC Section 625.42 as a continuous load (operating for 3 hours or more). Consequently, branch circuit conductors and overcurrent protection devices (breakers) must be sized at a minimum of 125% of the charger’s maximum rated continuous current (e.g., a 48A charger requires a 60A breaker and minimum 6 AWG copper rated at 75°C).